beautypg.com

Micrologix processor specifics – ProSoft Technology MVI69-DFNT User Manual

Page 161

background image

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 161 of 167

May 14, 2014

5.9

MicroLogix Processor Specifics

This section contains information specific to the MicroLogix processor based
family when used with the DF1 command set. The MicroLogix processor
commands support a file type field entered as a single character to denote the
data table to interface with in the command. This field is the same as that used
for a SLC processor. The following table defines the relationship of the file types
accepted by the module and the SLC file types:

5.9.1 SLC File Types

File Type

Description

S

Status

B

Bit

T

Timer

C

Counter

R

Control

N

Integer

F

Floating-point

Z

String

A

ASCII

The File Type Command Code is the ASCII character code value of the File Type
letter. This is the value to enter into the "File Type" parameter of the DF1
Command configurations in the data tables in the ladder logic.

Additionally, the SLC specific functions (502, 510 and 511) support a sub-
element field. This field selects a sub-element field in a complex data table. For
example, to obtain the current accumulated value for a counter or timer, the sub-
element field should be set to 2.

This manual is related to the following products: