beautypg.com

ProSoft Technology MVI69-DFNT User Manual

Page 54

background image

Ladder Logic

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 54 of 167

ProSoft Technology, Inc.

May 14, 2014

5 Click N

EXT

to continue.

6 Select the Requested Packet Interval value for scanning the I/O on the

module. This value represents the minimum frequency at which the module
will handle scheduled events. It should not be set to less than 1 millisecond.
Values between 5 and 10 milliseconds should work with most applications.

7 S

AVE

the module. Click OK to dismiss the dialog box. The Controller

Organization window now displays the module's presence. The following
illustration shows the Controller Organization window:

8 Copy the User-defined Data Types (UDTs) from the sample program.
9 Copy the Controller Tags from the sample program.
10 Copy the Ladder Rungs from the sample program.
11 Save and download the new application to the controller.

This manual is related to the following products: