5.5.3 Errors When EXT STS Is Present
Code (Int)
Code (Hex) Description
-4096
0xF000
Not used
-4095
0xF001
A field has an illegal value
-4094
0xF002
Less levels specified in address than minimum for any address
-4093
0xF003
More levels specified in address than system supports
-4092
0xF004
Symbol not found
-4091
0xF005
Symbol is of improper format
-4090
0xF006
Address does not point to something usable
-4089
0xF007
File is wrong size
-4088
0xF008
Cannot complete request
-4087
0xF009
Data or file is too large
-4086
0xF00A
Transaction size plus word address is too large
-4085
0xF00B
Access denied, improper privilege
-4084
0xF00C
Condition cannot be generated - resource is not available
-4083
0xF00D
Condition already exists - resource is already available
-4082
0xF00E
Command cannot be executed
-4081
0xF00F
Histogram overflow
-4080
0xF010
No access
-4079
0xF011
Illegal data type
-4078
0xF012
Invalid parameter or invalid data
-4077
0xF013
Address reference exists to deleted area
-4076
0xF014
Command execution failure for unknown reason
-4075
0xF015
Data conversion error
-4074
0xF016
Scanner not able to communicate with 1771 rack adapter
-4073
0xF017
Type mismatch
-4072
0xF018
1171 module response was not valid
-4071
0xF019
Duplicate label
-4070
0xF01A
File is open; another node owns it
-4069
0xF01B
Another node is the program owner
-4068
0xF01C
Reserved
-4067
0xF01D
Reserved
-4066
0xF01E
Data table element protection violation
-4065
0xF01F
Temporary internal problem