Module – ProSoft Technology MVI69-DFNT User Manual
Page 30

Configuring the MVI69-DFNT Module
MVI69-DFNT ♦ CompactLogix or MicroLogix Platform
User Manual
EtherNet/IP Client/Server Communication Module
Page 30 of 167
ProSoft Technology, Inc.
May 14, 2014
2.2
[Module]
This section describes how to initialize the module upon startup.
2.2.1 Failure Flag Count
0 through 65535
This parameter specifies the number of successive transfer errors that must
occur before halting communication on the application port(s). If the parameter is
set to 0, the application port(s) will continue to operate under all conditions. If the
value is set larger than 0 (1 to 65535), communications will cease if the specified
number of failures occur.
2.2.2 Initializing Output Data
Y
ES
or N
O
This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to N
O
(0), the output data will
be initialized to 0. If the value is set to Y
ES
(1), the data will be initialized with
data from the processor. Setting this option to Y
ES
requires associated ladder
logic to pass the data from the processor to the module.