MVI69-DFNT ♦ CompactLogix or MicroLogix Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 118 of 167

ProSoft Technology, Inc.

May 14, 2014

The M

ESSAGE

C

ONFIGURATION

dialog box must be completed to define the data

set to be transferred from the processor to the module. An example of the dialog
box follows:

Complete the dialog box for the data area to be transferred. For PLC5 and SLC
messages, the D

ESTINATION

E

LEMENT

should be an element in a data file (such

as, N10:0). For the PLC2 Unprotected Write message, the D

ESTINATION

E

LEMENT

is the address in the module’s internal database and cannot be set to a value
less than ten. This is not a limitation of the module but of the RSLogix software.
For a PLC2 unprotected write or read function, the database address should be
entered in octal format. Additionally, the C

OMMUNICATION

information must also

be configured. The following is an example of the dialog box.

Verify that the CIP

radio-button is selected as the

C

OMMUNICATION

M

ETHOD

. The

P

ATH

specifies the message route from the ControlLogix processor to the DFNT

module. Path elements are separated by commas. In the example path shown,
the first element is "Enet", which is the user-defined name given to the 1756-
ENET module in the chassis (you could substitute the slot number of the ENET
module for the name), the second element, "2", represents the Ethernet port on
the 1756-ENET module, and the last element of the path, "192.168.0.75", is the
IP address of the DFNT module, the target for the message.