ProSoft Technology MVI69E-MBS User Manual
Page 57

MVI69E-MBS ♦ CompactLogix Platform
MVI69E-MBS Configuration
Communication Module
User Manual
ProSoft Technology, Inc.
Page 57 of 162
January 6, 2014
Additional Configuration Parameters as a Slave
The Type parameter must be “Slave” or “PassThru Slave” to configure these
parameters. See “Configuration Parameters Common to Master and Slave” on
page xx.
Parameter
Value
Description
Minimum
Response Delay
0 to 65535
milliseconds
Sets the number of milliseconds to wait before responding to
a command received on the port from a remote Master. This
delay is sometimes required to accommodate slower Master
devices.
Internal Slave ID
1 to 247
Defines the Slave Node Address for the internal database. All
requests received by the port with this address are processed
by the module. Verify that each device has a unique address
on a network.
Bit Input Offset
0 to 9998
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 2
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.
Word Input
Offset
0 to 9998
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 4
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.
Output Offset
0 to 9998
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 1, 5 or 15
commands. For example, if the value is set to 100, an
address request of 0 corresponds to register 100 in the
database.
Holding Register
Offset
0 to 9998
Specifies the offset address in the internal Modbus database
for network requests for Modbus function 3, 6, or 16
commands. For example, if the value is set to 50, a request
for address 0 corresponds to the register 50 in the database.