Preset multiple registers (function code 16) – ProSoft Technology MVI69E-MBS User Manual
Page 124

Reference
MVI69E-MBS ♦ CompactLogix Platform
User Manual
Communication Module
Page 124 of 162
ProSoft Technology, Inc.
January 6, 2014
7.2.10 Preset Multiple Registers (Function Code 16)
Query
This Function Code allows you to modify the contents of a Modbus 4x range in
the slave. This writes up to 125 registers at time. Since the controller is actively
scanning, it also can alter the content of any holding register at any time.
Note: Function codes 5, 6, 15, and 16 are the only messages that are recognized as valid for
broadcast.
The example below is a request to write 2 registers starting at register 40002 in
slave 11.
Node
Addrs
Func
Code
Data Start
Addrs
High
Data Start
Addrs
Low
Number
of
Points
High
Number
of
Points
Low
Byte
Count
Data
High
Data
Low
Data
High
Data
Low
Error
Check
Field (2
bytes)
0B
10
00
01
00
02
04
00
0A
01
02
CRC
Response
The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.
Node
Address
Function
Code
Data Start
Address High
Data Start
Address Low
Number of
Points High
Number of
Points Low
Error Check
Field (2
bytes)
0B
10
00
01
00
02
CRC