beautypg.com

Force multiple coils (function code 15) – ProSoft Technology MVI69E-MBS User Manual

Page 123

background image

MVI69E-MBS ♦ CompactLogix Platform

Reference

Communication Module

User Manual

ProSoft Technology, Inc.

Page 123 of 162

January 6, 2014

7.2.9 Force Multiple Coils (Function Code 15)

Query
This Function Code forces each coil (Modbus 0x range) in a consecutive block of
coils to a desired ON or OFF state. Any coil that exists within the controller can
be forced to either state (ON or OFF). However, because the controller is actively
scanning, unless the coils are disabled, the controller can also alter the state of
the coil. Coils are numbered from zero (coil 00001 = zero, coil 00002 = one, and
so on). The desired status of each coil is packed in the data field, one bit for each
coil (1= ON, 0= OFF). The use of Slave address 0 (Broadcast Mode) forces all
attached Slaves to modify the desired coils.

Note: Functions 5, 6, 15, and 16 are the only messages (other than Loopback Diagnostic Test) that

are recognized as valid for broadcast.

The following example forces 10 coils starting at address 20 (13 HEX). The two
data fields, CD =1100 and 00 = 0000 000, indicate that coils 27, 26, 23, 22, and
20 are to be forced on.

Node

Address

Function

Code

Coil

Address
High

Coil

Address
Low

Number

of Coils
High

Number

of Coils
Low

Byte

Count

Force

Data
High 20

to 27

Force

Data
Low 28

to 29

Error

Check
Field (2

bytes)

0B

0F

00

13

00

0A

02

CD

01

CRC

Response
The normal response is an echo of the Slave address, function code, starting
address, and quantity of coils forced.

Node
Address

Function
Code

Coil
Address

High

Coil
Address

Low

Number of
Coils High

Number of
Coils Low

Error Check
Field (2 bytes)

0B

0F

00

13

00

0A

CRC

The writing of coils via Modbus function 15 is accomplished regardless of
whether the addressed coils are disabled or not.

Coils that are not programmed in the controller logic program are not
automatically cleared upon power up. Thus, if such a coil is set ON by function
code 15 and (even months later) an output is connected to that coil, the output is
hot.