beautypg.com

ProSoft Technology MVI69E-MBS User Manual

Page 143

background image

MVI69E-MBS ♦ CompactLogix Platform

Reference

Communication Module

User Manual

ProSoft Technology, Inc.

Page 143 of 162

January 6, 2014

7.4.14 Pass-through Formatted Block for Functions 6 and 16 with

Float Data Block

Block 9957: Pass-through Formatted Block for Functions 6 and 16 with Float
Data Block

Block 9957: Request from Module to Processor

Offset

Description

0

Read Block ID: 9957

1

Write Block ID: 9957

2

Number of word registers in Modbus data set

3

Starting address for Modbus data set

4 to (n+1)

Data (Length in words = n - 2)

Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.

The ladder logic is responsible for parsing and copying the received message
and performing the proper control operation as expected by the Master device.
The processor must then respond to the Pass-through block with a write block
with the following format.

Block 9957: Response from Processor to Module

Offset

Description

0

Write Block ID: 9957

1 to n

Spare (Length in words = n - 2)

This informs the module that the command has been processed and can be
cleared from the pass-through queue.