beautypg.com

Function blocks, 4 function blocks – ProSoft Technology MVI69E-MBS User Manual

Page 131

background image

MVI69E-MBS ♦ CompactLogix Platform

Reference

Communication Module

User Manual

ProSoft Technology, Inc.

Page 131 of 162

January 6, 2014

7.4

Function Blocks

Data contained in this database is paged through the input and output images by
coordination of the CompactLogix ladder logic and the MVI69E-MBS module's
program. Each block transferred from the module to the processor or from the
processor to the module contains a block identification code that describes the
content of the block.

Block ID Range

Description

-1000 to -1166

Get input image data for initialization

-1 to -999

Dummy block

0

Read or write data for small data sets

1 to 167

Read or write data

1000 to 1255

Event Command Port 1

2000 to 2255

Event Command Port 2

3000 to 3001

Port 1 slave polling control

3002 to 3006

Port 1 slave status

3100 to 3101

Port 2 slave polling control

3102 to 3106

Port 2 slave status

5001 to 5006

Port 1 Command Control

5101 to 5106

Port 2 Command Control

8000

Add Event with data for Port 1

8001

Add Event with data for Port 2

8100

Get Event with data status

9000 or -9000

Specifications of configuration file data from the processor to the module

9001 or -9001

Get configuration file from the processor to the module (continued)

9250

Get general module status data

9500

Set port and command active bits

9501

Get port and command active bits

9956

Pass-through formatted block for functions 6 and 16 with word data

9957

Pass-through formatted block for functions 6 and 16 with float data

9958

Pass-through formatted block for function 5

9959

Pass-through formatted block for function 15

9960

Pass-through formatted block for function 22

9961

Pass-through formatted block for function 23

9970

Pass-through block for function 99

9972

Set module time using received time

9973

Pass module time to processor

9997

Reset status block

9998

Warm-boot control block

9999

Cold-boot control block