beautypg.com

Retrotec DucTester 200 Series Residential Applications User Manual

Page 88

background image

Page 88 of 91
©Retrotec Inc. 2015

Total Duct Leakage Test Form (CA)

Test date: _______________/20____

Fan Model _______________Fan Serial # ______________ Digital gauge Serial # ___________________

Address: ________________________ Contact: _____________________ Phone: ______________

________________________________ Technician: ________________________________

The DucTester measures the total leakage of a duct system by pressurizing all ducts to 25 Pascals with
the air-handler off and the registers taped over.

Step

Detailed Description of the Step

1

Position DucTester near return

Ensure the flex will reach the return grill

2

Turn Air-handler off

Put your car keys beside the switch

3

Remove the furnace filter

Cover filter opening

4

Attach Flange + flex to return register

… or __access door in the air handler

6

Insert blue tube in a supply register

7

Seal all other registers

Do NOT seal to the wall or ceiling.

8

Open doors or windows

9

Connect the DucTester

__ yellow tube, __ power cord, __ speed control, __green tube.

10

Connect the DM-2

11

Turn on and set up the DM-2

12

Create a 25 Pa pressure in the ducts

13

Range Configuration


__ Low 1” nozzle, __Mid 2” nozzle, __Open inlet.

14

Record Flow and Pressure
Record Flow with @ 25 Pa displayed. Record n
and Time Avg displayed.

____ CFM, ___ Pa with NO @ Pressure displayed.
____ CFM, __ @ 25 feature used.
___ n and ___ seconds of Time Average displayed.

15


Record Flow Direction


___ pressurize with flow into ducts, __depressurize

16

Maximum Allowable duct leakage (per next
page) is:

____ CFM, ___ Pass, ___ Fail.

17

Remove tape

Remove tape from registers.

18

Turn HVAC equipment back ON

Re-install the furnace filter and turn all HVAC equipment back ON

Recording form based on CA Title 24