4. Set up the gauge to display Duct Leakage Results
Read the Total Duct Leakage results directly from the gauge. On the DM-2 this is the results display
”Mode”. In order to compare duct systems in different homes/buildings, it is necessary to normalize the
leakage results for the size of the HVAC system and the size of the building. The two most common
variables used to normalize duct leakage are total HVAC flow rate and the floor area of the building.
Figure 31: Some of the most common results that can be read directly off the gauge.
4.1 Mode setup for duct testing in the US
Table 3 shows what settings will directly calculate the results required for testing compliance with the
codes adopted in the various states.
Table 3: Gauge Mode Setup for US state Codes and programs for Duct Testing
Code
2009
IECC
ENERGY
STAR
Northwest
ENERGY STAR
Homes
Title-24
Code
WA State
Code
Region:
VT GA CT DE
GA ID IL IO
MA NC NH NJ
NY OH TX
MD
USA
ID MO OR WA
CA
WA
Pressure
Pa
Pa
Pa
Pa
Pa
Flow
CFM
CFM
CFM
CFM
CFM
(Flow) @ Pressure
@25 Pa
@25 Pa
@50 Pa
@25 Pa
@25 Pa
EqLA
Off
Off
Off
Off
Off
(EqLA) @ Pressure
n/a
n/a
n/a
n/a
n/a
EfLA, Effective Leakage
Area
Off
Off
Off
Off
Off