beautypg.com

Retrotec DucTester 200 Series Residential Applications User Manual

Page 62

background image

Page 62 of 91
©Retrotec Inc. 2015

CFM

25

multiplier for return = 1.22

CFM

25

multiplier for supply = 1.0 (default)

Leakage splits:

SLS = 200 CFM

25

/ 270 CFM

25

= 0.74

RLS = 70 CFM

25

/ 270 CFM

25

= 0.26

Loss Factors:

SLF = (0.74 x 1.0 x 1.22) = 0.9

RLF = (0.26 x 0.5 x 1.0) = 0.13

% HVAC System Loss =

270 CFM × (0.9+0.13)

1425 CFM

= 20%

Annual cooling loss = 20% x $1300 = $260

Annual heating loss = 20% x $ 500 = $100

Annual capacity loss = 20% x 3 ton = 0.6 tons

Annual operating SEER = (1 – 20%) x 11 SEER = 8.8 SEER