Table 12: Errors in Estimated Flow at 50 Pa if gauge "n"= 0.65 differs from actual n

Actual Flow Exponent (n) of Enclosure

0.50

0.55

0.60

0.65

0.70

0.75

Achieved

Pressure (Pa)

10

-21.4%

-14.9%

-7.7%

0.0%

8.4%

17.5%

15

-16.5%

-11.3%

-5.8%

0.0%

6.2%

12.8%

20

-12.8%

-8.8%

-4.5%

0.0%

4.7%

9.6%

25

-9.9%

-6.7%

-3.4%

0.0%

3.5%

7.2%

30

-7.4%

-5.0%

-2.5%

0.0%

2.6%

5.2%

35

-5.2%

-3.5%

-1.8%

0.0%

1.8%

3.6%

40

-3.3%

-2.2%

-1.1%

0.0%

1.1%

2.3%

45

-1.6%

-1.0%

-0.5%

0.0%

0.5%

1.1%

50

0.0%

0.0%

0.0%

0.0%

0.0%

0.0%

55

1.4%

1.0%

0.5%

0.0%

-0.5%

-0.9%

60

2.8%

1.8%

0.9%

0.0%

-0.9%

-1.8%

65

4.0%

2.7%

1.3%

0.0%

-1.3%

-2.6%

70

5.2%

3.4%

1.7%

0.0%

-1.7%

-3.3%

If the “n” value on the gauge is set to 0.60 and the enclosure n is different, an error, as shown in Table 13
will result if the [@ Pressure] function is used at the Achieved Pressure to estimate result at 50 Pa.

Table 13: Errors in Estimated Flow at 50 Pa if gauge "n" = 0.60 differs from actual n

Actual Flow Exponent (n) of Enclosure

0.50

0.55

0.60

0.65

0.70

0.75

Achieved

Pressure (Pa)

10

-14.9%

-7.7%

0.0%

8.4%

17.5%

27.3%

15

-11.3%

-5.8%

0.0%

6.2%

12.8%

19.8%

20

-8.8%

-4.5%

0.0%

4.7%

9.6%

14.7%

25

-6.7%

-3.4%

0.0%

3.5%

7.2%

11.0%

30

-5.0%

-2.5%

0.0%

2.6%

5.2%

8.0%

35

-3.5%

-1.8%

0.0%

1.8%

3.6%

5.5%

40

-2.2%

-1.1%

0.0%

1.1%

2.3%

3.4%

45

-1.0%

-0.5%

0.0%

0.5%

1.1%

1.6%

50

0.0%

0.0%

0.0%

0.0%

0.0%

0.0%

55

1.0%

0.5%

0.0%

-0.5%

-0.9%

-1.4%

60

1.8%

0.9%

0.0%

-0.9%

-1.8%

-2.7%

65

2.7%

1.3%

0.0%

-1.3%

-2.6%

-3.9%

70

3.4%

1.7%

0.0%

-1.7%

-3.3%

-4.9%

Achieved pressure is the actual maximum pressure achieved in the enclosure during the test.

𝐸𝑟𝑟𝑜𝑟 = (

𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝑜𝑓 𝐼𝑛𝑡𝑒𝑟𝑒𝑠𝑡

𝐴𝑐ℎ𝑖𝑒𝑣𝑒𝑑 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒

)

(𝐴𝑐𝑡𝑢𝑎𝑙 𝑛−𝐴𝑠𝑠𝑢𝑚𝑒𝑑 𝑛)