4. Change [Settings] for gauge operating parameters

Tapping [Settings] from the Home screen will bring up a menu that lists gauge settings. There are three
“Settings” screens, each displaying a number of gauge operating parameters that can be changed.

Figure 34: [Settings] can be changed on the gauge, and are remembered when the gauge is turned back on

More specifically, the [Settings] allows a user to:

acquire and apply bias pressure correction by tapping

[Baseline]

[Capture Baseline]

enter the conditioned

[Area]

or

[Volume]

(sometimes needed by “Result to be displayed”)

enter the number of seconds for

[Time averaging]

change the type of, and units for, the “Result to be displayed”

tap

[Network]

, then tap

[Status]

to toggle connection types and edit network credentials

set a [Default @ Pressure] for Result extrapolation when [Set Speed] is used

select the inactivity time (15 min, 30 min, 1 h, 2h, Off), after which the gauge powers itself down,

[Power down time]

. The gauge will not power itself down if “Off” is chosen.

enable or disable [Sound] feedback upon key press

set an appropriate “n” value, a slope for result extrapolation, with [Ducts=0.6, House=0.65]

update gauge firmware by tapping

[Firmware]

[Update Firmware]

(requires the DM32

Configurator software – refer to section 6)

Reset touchscreen sensitivity with

[Re-calibrate touchscreen]

For screen illustrations on using a function, click the hyperlinks in the above list.

4.1

Capture [Baseline] Pressure

Measure and remove bias/Baseline pressures due to wind or stack that are present before test pressures
are applied. The captured Baseline is subtracted from the pressure reading on [Channel A].

1. Tap [Capture Baseline] to begin sampling
2. Tap [End Capture] after 30 to 60 seconds. The displayed Baseline pressure is now subtracted from

all future readings on [Channel A]