beautypg.com

Ba a b b – MCZ Ego AIR User Manual

Page 23

background image

PELLET STOVES

Chapter 3

INSTALLATION AND USE MANUAL

page

23

Installation and fitting

Technical service - Rights reserved MCZ GROUP S.p.A. - Reproduction prohibited

When crossing through walls built with flammable materials, the

FITTER MUST suitably insulate the stove pipe crossing through it using

suitable insulating materials (thickness of 1.3-5 with min. heat

conductivity of 0.07 W/m°K).
The pipe introduced into the wall must however be suitably insulated to

avoid losing heat and soundproof the air outlet.

It is advisable to make ducts similar in length to

distribute the air in a uniform manner, otherwise the

hot air will opt for the shortest or less tortuous

ducting.

In the example in figures 6 and 7 (front and rear view), the air duct is

the same length for a total of 8 metres, in other words the piping (B)

will measure approximately 4 metres in length each. In the case of

different length ducts, the total must in any case always be a maximum
of 8 metres (for instance, 3 + 5 metres). In this case, the heat will be

distributed in the rooms unevenly.
The air in the room is recirculated through the perforated sheet situated

at the rear of the stove C and the holes on the panelled bottom.
It is possible for you to select the volume of air you wish to be released

from the front and from the rear of the stove independently, by

adjusting the power of the ventilation directly on the remote control.





Figure 6 – Air outlet system - front view

B

B

A

A

B

B

Figure 7 – Air outlet system - rear view

This manual is related to the following products: