background image

System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

Page 9 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

4) Specify rack spacing of 7U (12.25”) or 8U (14”) between trays and above top tray as required for

battery clearance. See table above.

5) Specify with or without Battery Disconnect circuit breakers. Note: All List 93 trays in a bay will be

furnished with or without Battery Disconnect circuit breakers as specified for the first tray ordered.

6) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from the following table.

Part Number

Ampere

Rating

Electrical/Mechanical Trip

1

(Black Handle) Electrical Trip

2

(White Handle)

50 256694300

256694400

60 256694700

256694800

70 256695100

256695200

75 256695500

256695600

100 256695900

256696000

125 100765

100762

150 100763

100764

200 121810

121809

Circuit Breaker Alarm Operation:

1

Provides an alarm during an electrical or manual trip condition.

2

Provides an alarm during an electrical trip condition only.


7) If ordering List 93 with circuit breakers, specify breaker mounting on left side or right side of tray.

Restrictions

Maximum number of List 93’s per bay is five (5).

A single List 93 must mount at bottom of bay. Multiple List 93’s must mount starting at bottom of bay and
working upward.