Features, Restrictions, Ordering notes – Emerson LXP48F1 User Manual
Page 21
System Application Guide
SAG582135000
Spec. No. 582135000 (Model LXP48F1)
Issue AE, January 31, 2007
Page 21 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Plug-In GMT Fuse Distribution Assembly (Part No. 528920)
(6) GMT Alarm-Type Fuse Positions
Features
♦ Mounts in (2) bullet nose distribution positions.
♦ 30A Maximum Capacity.
♦ Provides (6) Load Distribution Fuse Positions (0.25 to 15A GMT Alarm-Type Fuses).
♦ Screw clamp type terminals.
♦ Includes (6) dummy fuses equipped with safety fuse covers.
Restrictions
When factory-ordered, assembly will be installed in the two left-most bullet nose positions, unless otherwise
specified.
Maximum size of wire to be connected to a single fuse position is 14 AWG.
Fuses are not included.
Ordering Notes
1) Order Part No. 528920. Provides one Part No. 528958 alarm fuse distribution assembly, ground return
link, and hardware.
2) Order fuses, as required, per Table
Mounting Position for GMT