System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

Page 27 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Maximum

Current

(Amps)

Ambient

Operating

Temperature

(1)

Loop

Length (Ft)

1.0 Volt Drop

(2)

Loop

Length (Ft)

0.25 Volt Drop

(2)

Recm 90

°C

Wire Size

(1)

Recommended

Crimp Lug

(3)

163

40°C

36

9

(1) 2 AWG

(1) 245350800

155

50°C

38

9

(1) 2 AWG

(1) 245350800

110

65°C

54

13

(1) 2 AWG

(1) 245350800

Table 5

Recommended Battery Wire Size and Lug Selection

Notes to Tables 5:

1

Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved

National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-17 (Single-Insulated
Copper Conductors in Free Air) for wire rated at 90

°C conductor temperature operating in ambient

temperatures of 40

°C, 50°C and 65°C was used. For other operating ambient temperatures, refer to the

NEC. For operation in countries where the NEC is not recognized, follow applicable codes.

2

Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or

less, at rated full load output current of the shelf for the loop lengths shown in this column. Loop length is the
sum of the lengths of the positive and negative leads.

3

Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.