Dc input wire sizes and lugs—list ga, Features, Restrictions – Emerson LXP48F1 User Manual

Page 26: Ordering notes, Fer to table, For re

background image

SAG582135000

System Application Guide

Issue AE, January 31, 2007

Spec. No. 582135000 (Model LXP48F1)

Page 26 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Maximum

Current

(Amps)

Ambient

Operating

Temperature

(1)

Loop

Length (Ft)

1.0 Volt Drop

(2)

Loop

Length (Ft)

0.25 Volt Drop

(2)

Recm 90

°C

Wire Size

(1)

Recommended

Crimp Lug

(3)

List BB, BD, BL, BS, LB, LD, LS, LX

37

9

(3) 4 AWG

(3) 245346800

500 40°C

59

14

(3) 2 AWG

(3) 245350800

37

9

(3) 4 AWG

(3) 245346800

500 50°C

59

14

(3) 2 AWG

(3) 245350800

400

65°C

59

14

(3) 2 AWG

(3) 245350800

List GA

163

40°C

36

9

(1) 2 AWG

(1) 245350800

155

50°C

38

9

(1) 2 AWG

(1) 245350800

110

65°C

54

13

(1) 2 AWG

(1) 245350800

Table 5

Recommended Battery Wire Size and Lug Selection

Notes to Tables 5:

1

Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved

National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-17 (Single-Insulated
Copper Conductors in Free Air) for wire rated at 90

°C conductor temperature operating in ambient

temperatures of 40

°C, 50°C and 65°C was used. For other operating ambient temperatures, refer to the

NEC. For operation in countries where the NEC is not recognized, follow applicable codes.

2

Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or

less, at rated full load output current of the shelf for the loop lengths shown in this column. Loop length is the
sum of the lengths of the positive and negative leads.

3

Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.

DC Input Wire Sizes and Lugs—List GA

Features

♦ In the List GA Distribution Cabinet, lug-terminated battery conductors are connected to the battery terminals.

Captive nuts, (1/4-20 on 5/8" centers) are provided for installation of customer provided two-hole lugs.

♦ For lug mounting hole size and spacing dimensions, refer to the illustration provided in the

Physical Size

Information

section.

Restrictions

All lugs for customer connections must be ordered separately.

Customer must supply lug-mounting hardware.

Ordering Notes

1) Refer to Table

5

for recommended wire sizes and lugs at rated maximum Distribution Cabinet load.

When making connections, observe correct polarity.

2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.