7.0 Using an AGS Module

88

© 2012 Magnum Energy, Inc.

7.7.3 AGS Remote Fault Statuses

The following “Fault” statuses indicate that the generator wasn’t able to start

based on an expected autostart condition. Refer to

Section 7.8.3

“Resolving

AGS Faults Using the Remote” for help in diagnosing the problem.

Table 7-4, AGS Remote Fault Statuses

STATUS

DESCRIPTION

Gen Run Fault The generator successfully started and ran for more than

two minutes, but unexpectedly stopped before the AGS

could automatically stop the generator.

Fault Amp

The generator failed to start in Start Amps mode.

Fault Exercise The generator failed to start in Start Exercise mode.
Fault SOC

The generator failed to start in Start SOC mode.

Fault Temp

The generator failed to start in Start Temp mode.

Fault Test

The generator failed to start in Test mode.

Fault Time

The generator failed to start in Start Time mode.

Fault Topoff

The generator failed to start in Start Topoff mode.

Fault VDC

The generator failed to start in Start VDC mode.

Fault MaxRn

The generator turned off because the SETUP: 04F Max

Gen Run Time setting had been met. This fault can occur

when: 1) an autostop parameter has been met, but it

did not stop the generator, or, 2) the autostop condition

exceeded the Max Gen Run Time setting.

Menu Items

Default Settings

Gen Run VDC

Start Volts: 11.5 VDC (12v)

Start Volts Delay: 120 Sec

Stop Volts: 14.4 VDC (12v)

Stop Volts Delay: 120 Sec

Gen Run Time

OFF

Gen Run Amps*

OFF

Gen Run SOC

OFF

Gen Run Temp

OFF

Max Gen Run Time

12.0 Hrs

Quiet Time

OFF

Gen Exercise

OFF

Gen Warm-up Time

60 Sec

Gen Cooldown Time

60 Sec

*MS-PAE, MS-PE and MSH Series models only

Table 7-5, AGS Default Settings on ME-ARC