3.0 Setup

Table 3-1, ME-ARC Compatibility Matrix (cont.)

Button

FEATURES/SETTINGS

Model/

Level

Required

Default

Setting

Main

Menu

Menu

Heading/Item

Selections/

Adjustments Range

SETUP

04

AGS

Setup

(cont.)

04D Gen Run

SOC

OFF, Start Gen SOC= 20-90%

≥Level 1

[6]

OFF

Stop Gen SOC= 21-100%

04E Gen Run

Temp

Start=OFF, Ext Input, 65-95F

(18-35C)

≥Level 1

OFF

Time= 0.5-6.0 Hrs

04F Max Gen

Run Time

OFF, 0.1-25.5 Hrs

≥Level 1

12.0 Hrs

04G Quiet Time

OFF, ON= Start Quiet Time=

12:00A-12:00P

≥Level 1

OFF

Stop Quiet Time= 12:00A-

12:00P

Quiet Time Topoff=OFF, 30-

120 Min

04H Gen Ex-

ercise

Days=OFF, 1-255 days

≥Level 1

OFF

Run Hour/Min/AM-PM=

12:00A-12:00P

Run Time= 0.0-25.5 Hrs

04I Gen Warm-

up Time

0-127 sec, 1-127 min

≥Level 1

60 Sec

04J Gen

Cooldown time

0-127 sec, 1-127 min

≥Level 1

60 Sec

05

BMK

Setup

05A Charge Eff

Auto, 50-97%

≥Level 1

Auto

05B AmpHour

Size

200-2500 AH

≥Level 1

400 AH

* 12-volt values shown; for 24v systems – x 2, for 48v systems – x 4.
** These settings return to the factory default setting when power to the re-

mote is removed.
ME-ARC Compatibility Matrix Notes:
[1] Not available on MM/MM-E/MM-AE/MMS/MMS-E models.
[2] AC Couple Mode can be activated using Battery Type: Custom with MS-PAE

Series ≥Rev 4.1.
[3] The AC meter displays are only accurate when used with MS-PAE or MSH

Series inverters and aren’t shown unless the inverter is ≥ Level 4.
[4] Level 2 and 3 inverters can be used, but:

Level 2 inverters are limited from 1.0-4.5 hours,

Level 3 inverters

Level 3 inverters ≥Rev 4.1 (and MMS Rev 1.5) are limited from

1.5-6.5

hours;

Any setting outside these limited ranges are not recognized and

reverts to the inverter’s default absorption time (2.0 hrs).
[5] Requires ≥Level 4 to display.
[6] SOC features require the ME-BMK (Battery Monitor Kit) to be installed.
[7] To manually turn generator “ON” with remote, ME-AGS-N Rev 5.2 or higher

is required.