3.0 Setup

Table 3-1, ME-ARC Compatibility Matrix (cont.)

Button

FEATURES/SETTINGS

Model/

Level

Required

Default

Setting

Main

Menu

Menu

Heading/

Item

Selections/

Adjustments Range

SETUP

02

Invert

Setup

(cont.)

02E AC-In

SOC

Connect SOC= 20-98%

≥Level 3

[6]

50%

Disconnect SOC= 21-100%

100%

02F Power Up

Always

ON, OFF

≥Level 1

Always

OFF

03

Char-

ger

Setup

03A AC Input

Amps

AC/AC1 Input= 5-60A

≥Level 1 [1]

30A

AC2 Input= 5-60A

MSH-RE Models

20A

03B Battery

Type

Gel, Flooded, AGM, AGM2

≥Level 1

Flooded:

Absorb (12.0-16.0)*

≥Level 3

14.6*

Float (12.0-16.0)*

13.4*

EQ (12.0-16.0)*

15.5*

03C Max

Charge Rate

0-100%

≥Level 3

100%

03D VAC

Dropout

AC/AC1 Input= 60-100

VAC, UPS Mode

U.S. Models

80 VAC

AC2 Input= 60-100 VAC

MSH-RE Models

75 VAC

110-190 VAC, UPS Mode

Export models

150 VAC

03E Absorb

Done

Time= 0.1-25.5 Hrs

≥Level 4 [4]

2.0 Hrs

Amps= 0-150 ADC

≥Level 4 [5]

SOC= 50-100%

≥Level 4 [5] [6]

03F Max

Charge Time

0.0-25.5 Hrs

≥Level 4 [5]

12.0

Hrs

03G Final

Charge Stage

Multi, Float, Silent

≥Level 4 [5]

Multi

04

AGS

Setup

04A Gen Run

VDC

Start Gen Volts= 9.0-15.9*

≥Level 1

11.5

Start Volts Delay= 0-127

sec, 1-127 min

120 Sec

Stop Gen Volts= 9.1-

16.0*, Float

14.4

Stop Volts Delay=0-127

sec, 1-127 min

120 Sec

04B Gen Run

Time

OFF, ON= Start Gen

Time= 12:00A-12:00P

≥Level 1

OFF

Stop Gen Time= 12:00A-

12:00P

04C Gen Run

Amps

Start Gen AC Amps= OFF,

5-60A

≥Level 4

OFF

Start Amps Delay= 0-127

sec, 1-127 min
Stop Gen AC Amps=

5-60A
Stop Amps Delay= 0-127

sec, 1-127 min

Custom

[2]