Control circuit wiring, Control circuit connection diagram, Control circuit terminal block functions – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 70: 5 control circuit wiring

3.5 Control Circuit Wiring
u
Control Circuit Connection Diagram
Refer to
Figure 3.1
on page
53
when wiring terminals on the Z1000 Bypass and drive control circuits.
u
Control Circuit Terminal Block Functions
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a Z1000
Bypass with untested control circuits could result in death or serious injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter
Z1-01 may change the I/O terminal function automatically from the default setting.
Refer to Application Selection on page 108
to comply may result in death or serious injury.
The functions of the control circuit terminals are shown in
The control circuit terminals on Terminal Board A2 are arranged as shown in
12. SHIELD
11. SHIELD
10. IG24
9. IG24
8. DI-8
7. DI-7
6. DI-6
5. DI-5
4. DI-4
3. DI-3
2. DI-2
1. DI-1
TB2
TB3
4. SHIELD
3. TXRX-
2. TXRX+
1. IG5
TB1
12. DO-10 NO
11. DO-10 C
10. DO-10 NC
9. DO-9 NO
8. DO-9 C
7. DO-9 NC
6. DO-8 NO
5. DO-8 C
4. DO-8 NC
3. DO-7 NO
2. DO-7 C
1. DO-7 NC
Figure 3.19 Control Circuit Terminal Board A2 Arrangement
Table 3.7 Z1000 Bypass Control Circuit Terminal Board A2
Type
Signal Name
Description
Specification
Digital Inputs
DI-1
Digital Input 1
Dry contact rated, photocoupler sinking input to IG, 24 Vdc 8 mA,
ground fault protected
DI-2
Digital Input 2
DI-3
Digital Input 3
DI-4
Digital Input 4
DI-5
Digital Input 5
DI-6
Digital Input 6
DI-7
Digital Input 7
DI-8
Digital Input 8
IG24
Isolated Ground
Digital Input Common
3.5 Control Circuit Wiring
70
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual