Three-phase 480 vac models z1b1b001 to b034 – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 298

u
Three-Phase 480 Vac Models Z1B1B001 to B034
Table A.3 Power Ratings (Three-Phase 480 V)
Item
Specification
Bypass Model Z1B1
B001
B002
B003
B004
B007
B011
B014
B021
B027
B034
Maximum
Applicable
Motor
Capacity
HP
<1>
0.75
1
2
3
5
7.5
10
15
20
25
kW
0.55
0.74
1.5
2.2
3.7
5.5
7.5
11
14.7
18.4
Input
Input Current (A)
<2>
1.8
2.3
3.6
5.0
7.8
11.2
14.2
21.2
27.2
34.2
Rated Voltage
Rated Frequency
Three-phase 480 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Output
Rated Output Current (A)
1.6
<3>
2.1
<3>
3.4
<3>
4.8
<3>
7.6
<3>
11.0
<3>
14.0
<3>
21.0
<3>
27.0
<3>
34.0
<3>
Overload Tolerance
110% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage (V)
Three-phase 480 V
Maximum Output Frequency (Hz)
240 Hz
Harmonics
Reduction
DC Link Choke
Built-in
EMC
Filter (IEC/EN 61800-3 Category 2)
Built-in
<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or
greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
298
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual