B.15 defaults by drive model – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 352

Table B.5 480 V Default Settings by Model Selection
No.
Name
Unit
Default Settings
–
Bypass Model Z1B1
–
B001
B002
B003
B004
B007
B011
B014
B021
B027
o2-04
Drive Model Selection
Hex.
94
96
98
99
9A
9C
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
–
0.50
0.50
0.50
0.50
0.50
0.50
b3-11
Speed Search Method Switching Level (Speed
Estimation Type)
–
5.0
5.0
5.0
5.0
5.0
5.0
C6-02
Carrier Frequency Selection
–
2
2
2
2
2
2
E2-01
Motor Rated Current
A
4.80
7.60
11.00
14.00
21.0
27.0
E2-03
Motor No-Load Current
A
1.5
2.3
2.6
4
5.6
7.6
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.5
0.6
0.7
0.8
0.9
1.0
L2-05
Undervoltage Detection Level (Uv1)
–
380
380
380
380
380
380
L8-02
Overheat Alarm Level
°C
75
75
75
95
95
95
L8-06
Input Phase Detection Level
–
14.0
15.0
17.0
24.0
27.0
25.0
L8-09
Output Ground Fault Detection Selection
–
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction
–
2
2
2
2
2
2
No.
Name
Unit
Default Settings
–
Bypass Model Z1B1
–
B034
B040
B52L
B052
B065
B077
B096
o2-04
Drive Model Selection
Hex.
9D
9E
9F
or
(B0)
<1>
9F
or
(B0)
<1>
A1
or
(B1)
<2>
A2
or
(B2)
<3>
A3
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
100
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed
Search (Speed Estimation Type)
–
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b3-11
Speed Search Method Switching Level
(Speed Estimation Type)
–
5.0
5.0
5.0
5.0
5.0
5.0
5.0
C6-02
Carrier Frequency Selection
–
2
2
2
2
2
2
2
E2-01
Motor Rated Current
A
34.0
40.0
52.0
52.0
65.0
77.0
96.0
E2-03
Motor No-Load Current
A
7.8
9.2
10.9
10.9
19.1
22
24
L2-03
Momentary Power Loss Minimum
Baseblock Time
s
1.0
1.0
1.1
1.1
1.1
1.2
1.2
L2-05
Undervoltage Detection Level (Uv1)
–
380
380
380
380
380
380
380
L8-02
Overheat Alarm Level
°C
100
100
102
102
102
102
102
L8-06
Input Phase Detection Level
–
30.0
24.0
24.0
24.0
24.0
24.0
25.0
L8-09
Output Ground Fault Detection
Selection
–
0
0
1
1
1
1
1
L8-38
Carrier Frequency Reduction
–
2
2
2
2
2
2
2
<1> Set o2-04 to B0 for Z1000 chassis drives with Rev: B in the nameplate model field.
<2> Set o2-04 to B1 for Z1000 chassis drives with Rev: B in the nameplate model field.
<3> Set o2-04 to B2 for Z1000 chassis drives with Rev: B in the nameplate model field.
B.15 Defaults by Drive Model
352
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual