Bypass digital input terminal settings – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 207

No.
Name
Setting Range
Default
Z2-05
Digital Input 5 Function Select
0 to 36
25
Z2-06
Digital Input 6 Function Select
0 to 36
0
Z2-07
Digital Input 7 Function Select
0 to 36
0
Z2-08
Digital Input 8 Function Select
0 to 36
29
n
Bypass Digital Input Terminal Settings
Table 5.28 Bypass Digital Input Terminal Settings
Setting
Function
Page
0
<1>
Unused (Available for Serial Comms)
Note:
Multiple digital input terminals can
be programmed for “Unused
(Available for Serial Comms)”
(Z2-0o = 0). The drive will run only
when all digital inputs programmed
for “0” are active. This feature
applies to settings 0 and 22. Set all
other selections only once in
parameters Z2-01 to Z2-08.
3
DRV Multi-Function Input S3 (H1-03 Setting)
4
DRV Multi-Function Input S4 (H1-04 Setting)
5
DRV Multi-Function Input S5 (H1-05 Setting)
6
DRV Multi-Function Input S6 (H1-06 Setting)
7
DRV Multi-Function Input S7 (H1-07 Setting)
21
Run (AUTO Mode)
22
<1>
Run Enable (Safety)
Note:
Multiple digital input terminals can
be programmed for “Run Enable
(Safety)” (Z2-0o = 22) in bypass
controller software versions
VST800298 and later. The drive will
run only when all digital inputs
programmed for “22” are active.
This feature applies to settings 0 and
22. Set all other selections only once
in parameters Z2-01 to Z2-08.
Setting
Function
Page
23
Run Interlock (BAS)
24
Remote Transfer to Bypass
25
Smoke Purge Bypass Run to Destruction
26
Smoke Purge Drive Run to Destruction at Smoke
Purge Preset Speed
27
Motor OR Select
28
Motor AND Select
29
Motor 1 Overload Contact
30
Motor 2 Overload Contact
31
HAND Select
32
AUTO Select
33
DRIVE/BYPASS Select
34
Fault Reset
35
External Fault (EF0)
36
External Fault (EFB)
<1> Can be set to multiple digital input parameters simultaneously in bypass controller software versions VST800298 and later.
Setting 0: Unused (Available for Serial Comms)
Note:
Multiple digital input terminals can be programmed for “Unused (Available for Serial Comms)” (Z2-0o = 0). The drive will run only when
all digital inputs programmed for “0” are active. This feature applies to settings 0 and 22. All other selections should only be set once in
parameters Z2-01 to Z2-08.
Setting 3: DRV Multi-Function Input S3 (H1-03 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151
for available H1-03 multi-function input settings.
Setting 4: DRV Multi-Function Input S4 (H1-04 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151
for available H1-04 multi-function input settings.
Setting 5: DRV Multi-Function Input S5 (H1-05 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151
for available H1-05 multi-function input settings.
Setting 6:DRV Multi-Function Input S6 (H1-06 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151
for available H1-06 multi-function input settings.
Setting 7: DRV Multi-Function Input S7 (H1-07 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151
for available H1-07 multi-function input settings.
Setting 21: Run (AUTO Mode)
Starts and stops the bypass when Z1-08 is set to 1.
5.15 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
207
5
Programming