Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 347

No.
(Addr.
Hex)
Name
Description
Values
Page
Z2-09
(856B)
Digital Input 1 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-10
(856C)
Digital Input 2 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-11
(856D)
Digital Input 3 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-12
(856E)
Digital Input 4 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-13
(856F)
Digital Input 5 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-14
(8570)
Digital Input 6 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-15
(8571)
Digital Input 7 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-16
(8572)
Digital Input 8 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-23
(8579)
Digital Output 7 Function
Select
Digital Output 1 Function Select
0: Serial Comm Controlled
1: K1 Drive Input Contactor
2: K2 Drive Output Contactor
3: K3 Bypass Contactor
4: K4 Motor 1 Select
5: K5 Motor 2 Select
6: READY (Drive and Bypass)
7: RUN Active (Drive or Bypass)
8: Drive RUN Active
9: Bypass RUN Active
10: HAND Mode Active
11: OFF Mode Active
12: AUTO Mode Active
13: Drive Mode Selected
14: Bypass Mode Selected
15: Drive or Bypass Fault Active
16: Drive Fault Active
17: Bypass Fault Active
18: Auto Transfer Active
19: Serial RUN Command Active
20: Damper Actuator Output
21: ON Always
22: Loss of Load Detected
23: Run Verify
<1>
99: Not Used
Default: 7
Range: 0 to 23; 99
Z2-24
(857A)
Digital Output 8 Function
Select
Default: 10
Range: 0 to 23; 99
Z2-25
(857B)
Digital Output 9 Function
Select
Default: 12
Range: 0 to 23; 99
Z2-26
(857C)
Digital Output 10 Function
Select
Default: 15
Range: 0 to 23; 99
Z2-31
(8581)
<1>
Safety Open Message
Selection
Sets the fault message displayed when an FB01 fault is triggered.
0: Safety Open
1: Fire Stat
2: Freeze Stat
3: Smoke Alarm
4: Over Pressure
5: Low Suction
6: Vibration Switch
Default: 0
Range: 0 to 6
<1> Available in bypass controller software versions VST800298 and later.
B.14 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
347
B
Parameter List