Z4: bypass control option boards – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 349

u
Z4: Bypass Control Option Boards
No.
(Addr.
Hex)
Name
Description
Values
Page
Z4-01
(8700)
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Range: 0 to 255
Z4-02
(8701)
IP Address 2
Sets the second most significant octet of network static IP address.
Default: 168
Range: 0 to 255
Z4-03
(8702)
IP Address 3
Sets the third most significant octet of network static IP address.
Default: 1
Range: 0 to 255
Z4-04
(8703)
IP Address 4
Sets the fourth most significant octet of network static IP address.
Default: 20
Range: 0 to 255
Z4-05
(8704)
Subnet Mask 1
Sets the most significant octet of network static subnet mask.
Default: 255
Range: 0 to 255
Z4-06
(8705)
Subnet Mask 2
Sets the second most significant octet of network static subnet mask.
Default: 255
Range: 0 to 255
Z4-07
(8706)
Subnet Mask 3
Sets the third most significant octet of network static subnet mask.
Default: 255
Range: 0 to 255
Z4-08
(8707)
Subnet Mask 4
Sets the fourth most significant octet of network static subnet mask.
Default: 0
Range: 0 to 255
Z4-09
(8708)
Gateway IP Address 1
Sets the most significant octet of network gateway address.
Default: 192
Range: 0 to 255
Z4-10
(8709)
Gateway IP Address 2
Sets the second most significant octet of network gateway address.
Default: 168
Range: 0 to 255
Z4-11
(870A)
Gateway IP Address 3
Sets the third most significant octet of network gateway address.
Default: 1
Range: 0 to 255
Z4-12
(870B)
Gateway IP Address 4
Sets the fourth most significant octet of network gateway address.
Default: 1
Range: 0 to 255
Z4-13
(870C)
IP Address Mode Select
0: User-Defined (Static IP)
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
Z4-14
(870D)
Duplex Select
0: Forced Half Duplex
1: Auto Negotiate Duplex Mode and Communication Speed
2: Forced Full Duplex
Default: 1
Range: 0 to 2
Z4-15
(870E)
Speed Mode Setting
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
Z4-16
(870F)
Communication Loss
Timeout
Control connection timeout value for detection of communication loss.
Default: 0 s
Min.: 0
Max.: 300
Z4-17
(8710)
Ethernet Speed Scale
AC/DC Drive Object, Instance 1, Attribute 22
Default: 0
Min.: -15
Max.: 15