Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 214

n
Z4-13: Address Startup Mode
Selects the option address setting method.
No.
Name
Setting Range
Default
Z4-13
Address Startup Mode
0 to 2
2
Setting 0: User-Defined (Static IP)
Setting 1: BOOTP
Setting 2: DHCP
n
Z4-14: Duplex Mode Setting
No.
Name
Setting Range
Default
Z4-14
Duplex Mode Setting
0 to 2
1
Setting 0: Forced Half Duplex
Setting 1: Auto Negotiate Duplex Mode and Communication Speed
This setting also auto-negotiates Z4-15, Speed Mode Setting.
Setting 2: Forced Full Duplex
n
Z4-15: Speed Mode Setting
No.
Name
Setting Range
Default
Z4-15
Speed Mode Setting
10, 100
10
Setting 10: 10 Mbps
Setting 100: 100 Mbps
n
Z4-16: Timeout
Sets the Control Connection Timeout value for detection of communication loss in tenths of a second. A value of 0 disables
the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
No.
Name
Setting Range
Default
Z4-16
Timeout
0 to 300 s
0 s
n
Z4-17 to Z4-22: Scaling Factors
These parameters define scaling factors for drive monitors in the ODVA AC/DC Drive Object (Class 2AH), Instance 1, and
the attribute given below:
Speed Scale is attribute 22
Current Scale is attribute 23
Torque Scale is attribute 24
Power Scale is attribute 26
Voltage Scale is attribute 27
Time Scale is attribute 28.
No.
Parameter Name
Setting Range
Default
Z4-17
Speed Scaling
-15 to 15
0
Z4-18
Current Scaling
0
Z4-19
Torque Scaling
0
Z4-20
Power Scaling
0
Z4-21
Voltage Scaling
0
Z4-22
Time Scaling
0
n
Z4-23 to Z4-32: Dynamic Output Assembly Parameters
Parameters used in Output Assembly 116. Each parameter contains a MEMOBUS/Modbus address. The value received for
Output Assembly 116 will be written to this corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value received for Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
5.15 Z: Bypass Parameters
214
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual