Defaults by drive model, B.15 defaults by drive model – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 351

B.15 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table B.4 208 V Default Settings by Model Selection
No.
Name
Unit
Default Settings
–
Bypass Model Z1B1
–
D002
D003
D004
D007
D010
D016
D024
D031
D046
D059
D075
o2-04
Drive Model Selection
Hex.
66
68
6A
6B
6D
6E
6F
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b3-11
Speed Search Method Switching Level (Speed
Estimation Type)
–
5.0
5.0
5.0
5.0
5.0
5.0
5.0
C6-02
Carrier Frequency Selection
–
2
2
2
2
2
2
2
E2-01
Motor Rated Current
A
10.60
16.70
24.20
30.80
46.2
59.4
74.8
E2-03
Motor No-Load Current
A
3.00
4.50
5.10
8.00
11.2
15.2
15.7
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.5
0.6
0.7
0.8
0.9
1
1
L2-05
Undervoltage Detection Level (Uv1)
–
190
190
190
190
190
190
190
L8-02
Overheat Alarm Level
°C
80
80
105
105
110
110
115
L8-06
Input Phase Detection Level
–
16.0
21.0
15.0
18.0
22.0
23.0
24.0
L8-09
Output Ground Fault Detection Selection
–
0
0
0
0
0
0
1
L8-38
Carrier Frequency Reduction
–
2
2
2
2
2
2
2
No.
Name
Unit
Default Settings
–
Bypass Model Z1B1
–
D088
D114
D143
D169
D211
D273
o2-04
Drive Model Selection
Hex.
70
72
73
74
75
76
b3-04
V/f Gain during Speed Search
%
100
80
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.7
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
–
0.50
0.50
0.50
0.50
0.50
0.50
b3-11
Speed Search Method Switching Level (Speed
Estimation Type)
–
5.0
5.0
5.0
5.0
5.0
5.0
C6-02
Carrier Frequency Selection
–
2
2
2
2
2
2
E2-01
Motor Rated Current
A
88
114
143
169
211
273
E2-03
Motor No-Load Current
A
18.5
21.9
38.2
44.0
45.6
72.0
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1
1.1
1.1
1.2
1.3
1.5
L2-05
Undervoltage Detection Level (Uv1)
–
190
190
190
190
190
190
L8-02
Overheat Alarm Level
°C
115
115
109
109
109
109
L8-06
Input Phase Detection Level
–
24.0
25.0
28.0
26.0
28.0
28.0
L8-09
Output Ground Fault Detection Selection
–
1
1
1
1
1
1
L8-38
Carrier Frequency Reduction
–
2
2
2
2
2
2
B.15 Defaults by Drive Model
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
351
B
Parameter List