Start Up 4 - 6

9.

Press the S key once to display E2-01 “Motor Rated FLA”.

This parameter is the foundation of motor protection. It can be entered when auto-tuning is performed. Set this
parameter according to the motor rated current (FLA). Press the DATA/ENTER key once. Use the S, ▼ , and X
keys to adjust E2-01 to the motor rated full load amps.

Ensure the DATA/ENTER key is pressed to enter the value in the Drive. “Entry Accepted” briefly appears and your

display is now flashing.

10. Press the ESC once. Press DATA/ENTER once. Press S key twice to display b1-02 “Run Source”. This parameter

selects where the Drive will receive the run command. Press the DATA/ENTER key once. Use the

S or ▼ keys and

the DATA/ENTER key to set this parameter for the application.

Ensure the DATA/ENTER key is pressed to enter the selection in the Drive. “Entry Accepted” briefly appears and
the display is now not flashing.

11. Press the

▼ key once to display b1-01 “Reference Source”. This parameter selects where the Drive will receive the

speed command. Press the DATA/ENTER key once. Use the S or ▼ keys and the DATA/ENTER key to set this
parameter for the application.

Ensure the DATA/ENTER key is pressed to enter the selection in the Drive. “Entry Accepted” briefly appears and
the display is now not flashing.

12. Press the S key twice to display b1-03 “Stopping Method”.

This parameter selects the stopping method used when a stop command is given to the Drive.

Table 4.3 Motor Rated Current

Parameter

No.

Parameter Name

Digital Operator Display

Setting

Range

Factory

Setting

Menu

Location

E2-01

Motor Rated Current

Motor Rated FLA

kVA

Dependent

kVA

Dependent

Quick Setting

or

Programming

Table 4.4 Run Command Selection

Parameter

No.

Parameter Name

Digital Operator Display

Setting Choices

Setting

Range

Factory

Setting

Menu Location

b1-02

Run Command Selection

Run Source

0: Operator
1: Terminals
2: Serial Com
3: Option PCB

0 - 3

1

Quick Setting

or

Programming

Table 4.5 Speed Command Selection

Parameter

No.

Parameter Name

Digital Operator Display

Setting

Choices

Setting

Range

Factory

Setting

Menu Location

b1-01

Frequency Reference

Selection

Reference Source

0: Operator
1: Terminals
2: Serial Com
3: Option PCB

0 - 3

1

Quick Setting

or

Programming