Diagnostic & Troubleshooting 6 - 7

UV1

DC Bus Undervolt

DC Bus Undervoltage

The DC bus voltage is

≤ L2-05

208-240Vac: Trip point is

≤ 190Vdc

480Vac: Trip point is

≤ 380Vdc

Low input voltage at R/L1,
S/L2 and T/L3

Check the input circuit and
increase the input power to within
specifications

The acceleration time is set too
short

Extend the time in C1-01

Voltage fluctuation of the input
power is too large

Check the input voltage

UV2

CTL PS Undervolt

Control Power Supply Undervoltage
Undervoltage of the control circuit when
running

External load connected
pulling down the Drive power
supplies

Cycle power off and on to the
Drive

Repair or replace the Power PCB/
Gate Drive PCB

Remove all control wiring and
test Drive

UV3

MC Answerback

Soft Charge Circuit Fault
The pre-charge contactor opened while the
Drive was running

Contacts on the soft charge
contactor are dirty and the soft
charge contactor does not
function mechanically

Cycle power off and on to the
Drive

Check the condition of the soft
charge contactor

Repair or replace the Power PCB/
Gate Drive PCB

WARNING

Some features within the PI function group, cause the Drive to shut down momentarily (e.g. Sleep Function,
Snooze Function, Feedback Loss feature etc.) Upon recovery from the conditions that activate these features,
the Drive may start unexpectedly. Therefore, when enabling these features take appropriate measures to
notify personnel working with this equipment that unexpected starting may occur.

Table 6.1 Fault Displays and Processing

Digital

Operator Display

Description

Cause

Corrective Action