beautypg.com

480vac, Specifications c - 3 – Yaskawa P7 Drive User Manual User Manual

Page 213

background image

Specifications C - 3

‹

480Vac

Table C.2 480VAC Drive Specifications

Model Number CIMR-P7U

40P4

40P7

41P5

42P2

43P7

45P5

47P5

49P0

4011

4015

Rated output capacity (kVA)

1.4

1.6

2.8

4.0

5.8

9.5

13.0

16.0

21.0

26.0

Motor HP (460V)

0.5/0.75

1

1.5/2

3

5

7.5

10

15

20

25

Rated output current (A)

1.8

2.1

3.7

5.3

7.6

12.5

17.0

21.0

27.0

34.0

Max. output voltage (V)

3-phase; 380, 400, 415, 440, 460, or 480VAC (Proportional to input voltage.)

Max. output frequency (Hz)

120 Hz

Rated voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460 or 480VAC, 50/60 Hz

Rated input current (A)

2.2

2.5

4.4

6.4

9.0

15

20

26

33

40

Allowable voltage fluctuation

+ 10%, - 15%

Allowable frequency fluctuation

±5%

Measures for
power supply
harmonics

DC Reactor

Optional

12-pulse
Rectification

Not possible

Table C.2 480VAC Drive Specifications (Continued)

Model Number CIMR-P7U

4024

4030

4037

4045

4055

4075

4090

4110

4160

4185

4220

Rated output capacity (kVA)

40.0

51.0

59.0

73.0

95.0

120.0

140.0

180.0

230.0

315.0

390.0

Motor HP (460V)

40

50

60

75

100

125

150

200

250

300/350 400/450

Rated output current (A)

52.0

67.2

77.0

96.0

125.0

156.0

180.0

240.0

304.0

414.0

515.0

Max. output voltage (V)

3-phase, 380, 400, 415, 440, 460 or 480VAC (Proportional to input voltage)

Max. output frequency (Hz)

120 Hz

Max. voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460, or 480VAC, 50/60 Hz

Rated input current (A)

57

74

85

106

134

172

198

264

334

456

567

Allowable voltage fluctuation

+ 10%, - 15%

Allowable frequency fluctuation

±5%

Measures for
power supply
harmonics

DC Reactor

Built-in

12-Pulse
Rectification

Possible

Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the

Drive's rated output current is applicable for the motor's rated current.

A 3-wire phase-shifting transformer is required on the power supply for 12-pulse rectification.

Out

put r

ating

s

Power

s

upply char

acter

is

ti

cs

Cont

ro

l char

ac

te

ri

st

ic

s

Output r

ati

ngs

Power

s

upply char

acter

is

tics

Cont

ro

l char

ac

te

ri

st

ic

s