Parameters A - 18

Serial Com Setup

H5-01

Drive Node Address
Serial Comm Adr

Selects drive station node number (address) for
terminals R+, R-, S+, S-.*
An address of “0” disables serial com.

0 to FF

1F #

Programming

H5-02

Communication Speed Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud

0 to 4

3

Programming

H5-03

Communication Parity Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-,
S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

H5-04

Stopping Method after
Communication Error
Serial Fault Sel

Selects the stopping method when a communication
error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

H5-05

Communication Error Detection
Selection
Serial Flt Dtct

Enables or disables the communications timeout
detection function.
0: Disabled - A communications loss will NOT cause a

communications fault.

1: Enabled - If communications are lost for more than

the time specified in parameter H5-09,
a communications fault will occur.

0 or 1

1

Programming

H5-06

Drive Transmit Wait Time
Transmit WaitTIM

Sets the time from when the drive receives data to when
the drive sends data.

5 to 65

5ms

Programming

H5-07

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

1

Programming

H5-09

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost
before a fault is annunciated. Works in conjunction with
parameters H5-05 and H5-04.

0 to 10.0

(H5-08=0)

0 to 10.0

2.0sec

Programming

Motor Overload

L1-01

Motor Overload Protection
Selection
MOL Fault Select

Enables or disables the motor thermal overload

protection.

0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor

0 to 1

1

Programming

L1-02

Motor Overload Protection
Time
MOL Time Const

Determines how much time will elapse prior to a motor
overload fault (OL1), when motor amps exceed the
value set in parameter E2-01 by 10%. Actual (OL1) trip
time will vary depending on severity of overload.

0.1 to 20.0

8.0min

Programming

L1-03

Motor Overheat Alarm Operation
Selection
Mtr OH Alarm Sel

Operation selection when the motor temperature analog
input (H3-09=E) exceeds the OH3 alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

L1-04

Motor Overheat Fault Operation
Selection
Mtr OH Fault Sel

Stopping method when the motor temperature analog
input (H3-09=E) exceeds the OH4 level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

1

Programming

L1-05

Motor Temperature Input Filter
Time
Mtr Temp Filter

Delay Time applied to motor temperature analog input
(H3-09=E) for filtering purposes.

0.00 to

10.00

0.20sec

Programming

Denotes that parameter can be changed when the drive is running.
* After these parameters are changed, drive power must be cycled before the changes will take effect.
# Hex, see page A-30.

Table 1:

Parameter List (Continued

)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu