Parameters a - 4, Sequence, Table 1: parameter list (continued) – Yaskawa P7 Drive User Manual User Manual
Page 178

Parameters A - 4
Sequence
b1-01
Frequency Reference
Selection
Reference Source
Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
0 to 3
1
Quick Setting
b1-02
Run Command Selection
Run Source
Selects the run command input source.
0: Operator - “Run” and “Stop” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
0 to 3
1
Quick Setting
b1-03
Stopping Method Selection
Stopping Method
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if input before
the time in C1-02 expires.)
0 to 3
0
Quick Setting
b1-04
Reverse Operation Selection
Reverse Oper
Determines the forward rotation of the motor, and if reverse opera-
tion is disabled.
0: Reverse Enabled
1: Reverse Disabled
2: Exchange Phase - Change direction of forward motor rotation.
3: ExchgPhs, Rev Dsbl - Change direction of forward motor
rotation and disable reverse operation.
0 to 3
1
Programming
b1-07
Local/Remote Run Selection
LOC/REM RUN Sel
0: Cycle Extern RUN - If the run command is closed when
switching from hand(local) mode to auto(remote) mode, the
drive will not run.
1: Accept Extrn RUN - If the run command is closed when
switching from hand(local) mode to auto(remote) mode, the
drive WILL run.
0 or 1
0
Programming
b1-08
Run Command Selection
During Program
RUN CMD at PRG
0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus
(except when b1-02 = 0).
0 or 1
0
Programming
b1-11
Drive Delay Time Setting
Wait to Run Time
After a run command, drive output will start after this delay time.
0 to 600
0sec
Programming
b1-12
Hand Frequency Reference
Selection
HAND Fref Source
Selects the speed command input source in hand mode.*
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
0 or 1
0
Programming
b1-13
HAND/AUTO During Run
Selection
HAND/AUTO @Run
Selects if drive will permit switching between HAND and AUTO
modes while running.
0: Disabled
1: Enabled
0 or 1
0
Programming
b1-14
Emergency Override Speed
E Override Speed
Sets the speed command used in emergency override mode when
b1-15=0.
0.00 to
120.00 Hz
0.00
Programming
b1-15
Emergency Override
Reference Selection
E OverrideRefSel
Selects the emergency override reverse source.
0: Use b1-14 Ref
1: Use AUTO Ref
0 or 1
0
Programming
Table 1: Parameter List (Continued)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location