Parameters a - 26, Monitor – Yaskawa P7 Drive User Manual User Manual
Page 200

Parameters A - 26
Monitor
U1-13
Cumulative Operation Time
Elapsed Time
Displays total operating or power-on time of the Drive.
U1-14
Software Number
FLASH ID
Displays Drive's software number.
U1-15
Terminal A1 Input Voltage
Term A1 Level
Displays the input voltage on Terminal A1, as a percentage of 10V
DC.
U1-16
Terminal A2 Input Voltage
Term A2 level
Displays the input current (or voltage) on Terminal A2, as a per-
centage of 20mA (or 10 V DC).
U1-18
Motor Secondary Current (I
q
)
Mot SEC Current
Displays the amount of current being used by the motor to pro-
duce torque (Iq).
U1-20
Output Frequency After Soft
Start
SFS Output
Displays the frequency reference (speed command) after the accel
and decel ramps.
U1-24
PI Feedback Value
PI Feedback
Displays the feedback signal when PI control is used.
U1-28
CPU Number
CPU ID
Displays control board hardware revision.
U1-29
kWh
kWh Lo 4 Digits
Displays the accumulated kWh.
U1-30
MWh
kWh Hi 5 Digits
Displays the accumulated MWh.
U1-34
First Parameter Causing an
OPE
OPE Detected
Displays the parameter number causing an “OPE” fault.
U1-36
PI Input
PI Input
Displays the “error” in the PI regulator. (U1-36 = PI Setpoint - PI
Feedback)
U1-37
PI Output
PI Output
Displays the output of the PI as a percentage of maximum fre-
quency (E1-04).
U1-38
PI Setpoint
PI Setpoint
Displays the setpoint of the PI regulator (U1-38 = PI reference + PI
bias)
U1-39
Memobus Communication
Error Code
Transmit Err
U1-40
Heatsink Cooling Fan Opera-
tion Time
FAN Elapsed Time
Displays total operating time of the heatsink cooling fan.
U1-51
Auto Mode Frequency Refer-
ence Value
Auto Mode Fref
Displays the frequency reference (speed command) when in auto
mode.
U1-52
Hand Mode Frequency Ref-
erence Value
HAND Mode Fref
Displays the frequency reference (speed command) when in hand
mode, or displays Terminal A2 when differential mode is selected.
U1-53
PI Feedback 2 Value
PI Feedback 2
Displays PI feedback 2 value.
Parameter
No.
Parameter Name
Digital Operator Display
Description
1: CRC error
1: Data length error
Not used. Always 0.
1: Parity error
1: Overrun error
1: Fleming error
1: Timeover
Not used. Always 0
.
0 0 0 0 0 0 0 0