Monitor list, Parameters a - 25, Monitor – Yaskawa P7 Drive User Manual User Manual

Page 199

background image

Parameters A - 25

Monitor List

Table 2: Monitor List

Parameter

No.

Parameter Name

Digital Operator Display

Description

Monitor

U1-01

Frequency Reference
Frequency Ref

Frequency reference (speed command) monitor when in auto
mode, frequency reference (speed command) setting location when
in hand mode. Units changeable via o1-03.

U1-02

Output Frequency
Output Freq

Output frequency (speed) monitor. Units changeable via o1-
03.

U1-03

Output Current
Output Current

Output current monitor

U1-06

Output Voltage
Output Voltage

Displays Drive output voltage

U1-07

DC Bus Voltage
DC Bus Voltage

Displays DC Bus Voltage

U1-08

Output Power
Output kWatts

Displays Drive output power

U1-10

Input Terminal Status
Input Term Sts

Displays Drive input terminal status

U1-11

Output Terminal Status
Output Term Sts

Output terminal ON/OFF Check

U1-12

Drive Operation Status
Int Ctl Sts 1

0

1: FWD. run

(Terminal S1) is ON.

1: REV. run

(Terminal S2) is ON.

1: Multi-function input 1

(Terminal S3) is ON.

1: Multi-function input 2

(Terminal S4) is ON.

1: Multi-function input 3

(Terminal S5) is ON.

1: Multi-function input 4

(Terminal S6) is ON.

1: Multi-function input 5

(Terminal S7) is ON.

0 0 0 0 0 0 0

1: Multi-function Contact 1

output 1 (Terminal M1-M2)

is ON

1: Multi-function Contact 2

output 1 (Terminal M3-M4)

is ON

Not used

1: Fault output

(Terminal MA/MB-MC) is

ON

0 0 0 0 0 0 0 0

1: During running

1: During zero speed

1: During reverse

1: During reset signal input

1: During speed agree

1: Drive operation ready

1: During fault detection

(Minor fault)

1: During fault detection

(Major fault)

0 0 0 0 0 0 0 0