Z1000u bypass quick start procedure, Bacnet communications (optional) (continued) – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 33
YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass
Quick Start Procedure
Page 33
of 37
13.3 Terminate the end nodes of the BACnet network.
Terminate the two ends of the BACnet network line with a 120 ohm resistor between the TXRX+ and TXRX signals. The Z1000U Bypass
has a built in termination resistor that is enabled or disabled using DIP switch S1 located on the bypass control board.
Enable the termination resistor by setting DIP switch S1 to the ON position if the bypass is located at the end of a network line.
Disable the termination resistor on all bypass slaves that are not located at the network line end.
13.4 Set these Parameters
•
Z3-01 = 3 (Serial Communications Protocol Select = BACNet)
•
Z3-02 = Unique MAC address number (No two devices on the MS/TP BACnet network can be the same.)
•
Z3-03 = Baud Rate (Set all devices on the BACnet network for the same baud rate)
•
Z3-04 = 0 (No Parity)
•
Z3-05 = 0 or 1 (Ignore or Alarm Only. Set time to alarm using parameter Z3-06.)
•
Z3-08 and Z3-09 = BACnet Object ID number (in hexadecimal) (No two devices on the entire BACnet network (MS/TP and
BACnet/IP) may have the same BACnet Object ID number.)
13.5 Cycle Incoming Power
Z1000U Bypass main input power must be de-energized and remain off until all HOA keypad indications are extinguished. This
process stores and saves the Z3 parameter settings.
Commonly Used Objects for Monitoring a Bypass
Object ID
Description (Object Name)
AV10
Drive Output Frequency (Output Frequency)
AV12
Drive Output Current (Output Current)
AV13
Drive Output Power (Output Power)
AI10
Output Current During Bypass (Motor Current UB-01)
BV89
Run Status, drive and bypass (BYP Run Status)
BV90
Fault Status, drive and bypass (BYP Fault Status)
BV83
In Drive Mode (BYP DRV Mode Status)
BV84
In Bypass Mode (BYP BYPASS Mode Stat)
BACnet Communications (OPTIONAL) (continued)
13
STEP