YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass
Quick Start Procedure
Page 10
of 37
This fi gure illustrates locations of the Bypass Control Board terminal blocks.
Note: The Bypass Control Board mounting location varies slightly by model.
E(G) IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC
24V
RP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
Line
L1 L2 L3
Motor
T1 T2 T3
12. SHIELD
11. SHIELD
10. IG24
9. IG24
8. DI-8
7. DI-7
6. DI-6
5. DI-5
4. DI-4
3. DI-3 Run Interlock (BAS)
2. DI-2 Run Enable (Safety)
1. DI-1 Run (Auto Mode)
TB2
TB3
TB1
A
Bypass
Control
Board
Jumper
or
switch
Auto-RUN
Closed to RUN
(Customer
supplied)
NOTICE: Equipment Malfunction. Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, p1, n1, U/T1, V/T2,
W/T3) and other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
5.1 Initial power application.
Follow these precautions prior to energizing the bypass.
Remove tools: Remove all tools and debris is from the enclosure.
Check wiring: Verify correct termination of main and motor power connections.
Check main supply: Verify correct input voltage at main switch or breaker is present.
Clear personnel: Ensure all personnel are clear of drive and motor and motor shaft is free to rotate.
Locate power off: Be familiar with emergency power off switch/breaker location.
Wire Interlock Circuits (continued)