YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass
Quick Start Procedure
Page 14
of 37
7.5 AUTO REF: Confi gure the Frequency Reference via Remote Analog Input.
NOTICE: Equipment Damage Tighten terminal screws to specifi ed torque. Failure to comply may result in erroneous operation or
damage to the terminal block.
NOTICE: Separate the control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, p1, n1, U/T1, V/T2, W/T3). Improper
wiring practices could result in drive malfunction due to electrical interference.
Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could result
in drive or equipment malfunction due to short circuit. Use shielded twisted-pair cables as indicated to prevent operating faults. Improper
wiring practices could result in drive or equipment malfunction due to electrical interference.
Connect the cable shield to the appropriate ground terminal. Improper equipment grounding could result in drive or equipment
malfunction or nuisance trips. The shield ground wire (F) is typically connected at one end, at the signal source to avoid ground loops.
Use terminal (Drive Terminal Board TB5) if a shield ground connection is required at the drive to mitigate noise issues in special cases.
7.6 Connect remote frequency reference wires to the drive control circuit terminals.
A
B
C
D
E
Preparing the Ends of Shielded Cables
F
A – Drive side
B – Shield
C – Insulation
D – Control device side
E – Shield sheath (insulate with tape)
F – Shield wire to E(G) or
single terminal TB5
TB3 Typical Analog Frequency Reference Input Connections (Choose one)
0 ~ 10 Vdc
4 ~ 20 mA
+
-
E(G)
or
TB5
Cable
Shield
+
-
E(G)
or
TB5
Cable
Shield
+V AC A1 A2 A3 FM AM AC
+V AC A1 A2 A3 FM AM AC
Potentiometer 2kΩ
+V AC A1 A2 A3 FM AM AC
E(G) IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC
24V
RP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
E(G) IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC
24V
RP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
TB5
Drive Terminal Board
No.
Terminal Name (Function)
Signal Types
+V
Power supply for analog inputs
10.5 Vdc (maximum allowable current 20 mA)
A1
Multi-function analog input 1
•
(Default: 0 to 10 Vdc)
Other supported signal types:
•
-10 to 10 Vdc, input impedance: 20 k
Ω
•
4 to 20 mA, 0 to 20 mA (input impedance: 250
Ω
•
Voltage or current input must be selected by jumper S1 and H3-01.
Note: Used for 0 to 10 V AUTO frequency reference
A2
Multi-function analog input 2
•
(Default 4 to 20 mA)
Other supported signal types:
•
0 to 20 mA input impedance: 250
Ω
•
0 to 10 Vdc, -10 to 10 Vdc, input impedance: 20 k
Ω
•
Voltage or current input must be selected by jumper S1 and H3-09.
Note: Used for 4 to 20 mA AUTO frequency reference
AC
Frequency reference common
0 V
E (G) Ground for shielded lines
—
Confi gure the HAND and AUTO Frequency Reference (continued)
7