Z1000u bypass quick start procedure, Hoa keypad tutorial (continued), Confi gure the hand and auto frequency reference – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 12: Freq ref (auto), Page 12 of 37

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass 
Quick Start Procedure
Page 12
of 37
•
The HAND and AUTO frequency references can be set independently.
•
The factory default for HAND frequency reference originates from the HOA keypad.
•
The factory default for AUTO frequency reference originates from drive analog inputs A1 or A2.
7.1 Ensure the HOA keypad cable is fi rmly connected between the HOA keypad door mounted
cable port and communications port CN2 on the bypass controller board.
7.2 Energize the Bypass.
HOA Keypad Tutorial (continued)
6
STEP
Confi gure the HAND and AUTO Frequency Reference
7
STEP
Display
FUNCTION KEY 1 (F1)
HELP
Press F1 to display the Help menu.
<--
Press F1 to scroll the cursor to the left.
HOME
Press F1 to return to the top menu 
(Frequency Reference).
ESC
Press F1 to return to the previous 
display.
RLY
Press F1 to select/deselect Drive Test 
Mode. During Drive Test Mode, power 
is applied to the drive while in Bypass 
Mode by forcing the drive input contac-
tor to close (3-contactor bypass only).
㼉
㼉
Freq Ref (AUTO)
Display
BYPASS STATUS DISPLAY
AUTO XFER EN Running in Auto Transfer,
a fault was detected and 
switched to Bypass Mode.
ENRGY SAVE EN Running in Energy Savings
Mode
MTR STOPPING Fault is removed but motor is
still ramping down.
FAULTED
Fault has been detected caus-
ing motor output contactors 
to open.
Display
BYPASS STATUS DISPLAY
POWERUP
Bypass is powering up.
OFF
No Run command is present and 
the safety circuit is closed.
WAIT FOR RUN
AUTO mode: 
-Safety circuit is closed
-Bypass waits for Run input.
SAFETY OPEN
The safety circuit input is open.
INTRLOCK OPN
Run command is present, the 
safety circuit is closed, but the 
Interlock input is open.
PRE RUN DRIVE
Bypass is running in the Pre-Run 
State at the programmed fre-
quency for the programmed time.
RUN DRIVE
Running in Drive Mode.
RUN BYPASS
Running in Bypass Mode.
RMOT XFER EN
Running in Remote Transfer.
SMOK PRG BYP
Running in Smoke Purge Bypass.
SMOK PRG DRV
Running in Smoke Purge Drive.
Display
DATA DISPLAY
—
Displays specifi c data and operation 
data.
Display
AUTO/HAND Display
AUTO
AUTO or OFF Mode (running or stopped).
HAND
HAND Mode
Display
AUTO/HAND Display
RSEQ
RREF
AUTO Mode (running or stopped).
LSEQ
LREF
HAND or OFF Mode.
Display
FUNCTION KEY 2 (F2)
DATA
Press F2 to scroll to the next display.
-->
Press F2 to scroll the cursor to the 
right.
DRV/BYP
Press F2 to toggle selection between 
Bypass Mode and Drive Mode
Display
BYPASS/DRIVE STATUS
DISPLAY
DRV
(not blinking)
Drive Mode. The bypass will run in 
Drive Mode when a Run command 
is present.
DRV
(blinking)
Drive Mode, but a condition is 
making the bypass run in Bypass 
Mode. Example: Smoke Purge - 
Bypass Mode
BYP
(not blinking)
Bypass Mode. The bypass will run 
in Bypass Mode when a Run com-
mand is present. In a three-contac-
tor bypass, drive input contactor 
K1 is open and the drive will be 
powered down.
BYP
(blinking)
Bypass Mode with Drive Test Mode 
set. The bypass will run in Bypass 
Mode when a Run command 
is present. In a three-contactor 
bypass, drive input contactor K1 is 
closed and the drive is powered on.
