Problem/Symptom

Solution

Drive Will Not Start

AUTO LED is OFF and DRV-OFF on HOA Keypad

Bypass is not in AUTO

DRV-OFF
is displayed and
AUTO key LED
is OFF.

DRV-OFF

Press

to put the bypass in AUTO Mode.

Set Z1-06 to 1 (Power-Up Mode is AUTO-DRIVE) and cycle power to put
the bypass in AUTO Mode at power-up.

Problem/Symptom

Solution

Drive Will Not Start

AUTO LED Is Blinking Green and WAIT FOR RUN is
displayed on the HOA Keypad

Verify Bypass Control Board circuit TB2-1 to 10 is closed.

Troubleshooting (continued)

12

STEP