Z1000u bypass quick start procedure, Page 3 of 37, Safety symbols in this document warning – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 3: Warning

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass 
Quick Start Procedure
Page 3
of 37
Safety Symbols in 
this Document
WARNING!
Read and understand 
users manual before 
using this equipment. 
Failure to follow users 
instructions may result 
in serious injury or 
death.
WARNING!
Hazardous Voltage. 
Contact may cause 
electric shock or burn. 
Turn-off and lock-out 
system and facility 
power before servicing.
WARNING!
Stay Clear- Equipment 
starts automatically. 
Clear all personnel 
from equipment, install 
shields or guards, locate 
and verify emergency 
SHUT-OFF is functional. 
Failure to comply may 
result in serious injury 
to personnel.
WARNING!
Improper Operation 
Sequence. DO NOT 
RUN THE MOTOR. 
Failure to comply may 
result in serious injury 
to personnel.
WARNING!
Do not operate 
equipment with covers 
or guards removed. 
Install or replace cover 
and/or guards before 
operation. Failure to 
comply may result 
in serious injury to 
personnel.
This Z1000U Quick Start Procedure serves as general guide to help install, confi gure and perform test run 
operation. Refer to Z1000U Bypass Technical Manual No. SIEPYAIZ1D01 for complete instructions and to 
confi gure the Z1000U Bypass for each specifi c installation site.
1.1 Verify the correct Z1000U Bypass model and ratings.
a. Locate the Z1000U Bypass nameplate and your order information.
b. Verify the Z1000U Bypass Model No: (E) matches the line item(s) on your order, to confi rm receipt of 
the correct model.
c.
Locate the nameplate of motor that will be connected to the Z1000U Bypass.
d. Confi rm the motor nameplate Amperage, Voltage, and Frequency (Hz) are within the Output
specifi cations (B) shown on the Z1000U Bypass nameplate.
A- Input specifications
B- Output specifications
C- Control transformer fuse specs
D- Serial number
E- Bypass model number
F- Schematic document number
A
A.C. INPUT
A.C. OUTPUT
Designator Rating
Serial No.:4W14Z5747540001
Model No. :Z1D1D002PM
Type: Z1000U BYPASS
W.D.: DS.Z1D1.01
Inst. Manual:SIEPYAIZ1D01,
TOEPC71063611
F1,F2
FNQ-R
1.5A,600V
Type
Volts: 480
Volts: 0-460
Hz: 50/60
Hz: 0-60
Phase: 3
Phase: 3
SCCR: 65kA rms sym.,480V max.
Amps:114.0
Amps:124.0
B
F
C
D
E
1.2 Verify main power source is adequate by reviewing the Input
specifi cations (A) shown on the Z1000U Bypass nameplate.
Z1000U Bypass Model Identifi cation and Installation
1
STEP