Z1000u bypass quick start procedure, Troubleshooting, Page 30 of 37 – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 30

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass
Quick Start Procedure
Page 30
of 37
Problem/Symptom
Solution
AL02 Fault in HOA Keypad - BAS interlock Open
Bypass Control Board terminal block TB2-3 to 10 is open.
Close contact TB2-3 to 10.
Problem/Symptom
Solution
FB01 Fault in HOA Keypad – Run Enable/Safety Fault
Bypass Control Board terminal block TB2-2 to 10 is open.
Close contact TB2-2 to 10.
Problem/Symptom
Solution
Drive Will Not accelerate the motor to speed.
U1-01 on HOA keypad indicates 0.00 Hz.
The drive is not receiving a frequency reference.
If the desired reference source is ANALOG: Verify Z1-07 = 1 (Speed
Reference Select is set to Analog Input) and verify analog signals at
terminals.
0 ~ 10 Vdc
4 ~ 20 mA
+
-
E(G)
or
TB5
Cable
Shield
+
-
E(G)
or
TB5
Cable
Shield
+V AC A1 A2 A3 FM AM AC
+V AC A1 A2 A3 FM AM AC
Potentiometer 2kΩ
+V AC A1 A2 A3 FM AM AC
TB3 Typical Analog Frequency Reference Input Connections (Choose one)
If the desired reference source is DIGITAL: Verify Z1-07 = 0 (Speed
Reference Select set to Operator) and Z1-09 = Fref (HAND Mode Drive
Speed Reference) is a non-zero value. Refer to the Bypass Technical
Manual for other reference sources, such as serial communications or
PID.
Troubleshooting
12
STEP
11.3 This section provides information to assist in solving common problems that may
occur during test run operation.