Z1000u bypass quick start procedure, Verify common parameters (continued) – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 20

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass
Quick Start Procedure
Page 20
of 37
Parameter
HOA Menu
Access
Default
Value
Description
HOA Display
Comments
Z1-08
1
Run Command Select
Run Cmd Sel
Determines the source of the Auto Mode Run
command used by the Bypass Controller.
0: Operator
1: Bypass Controller Digital Input
2: Bypass Serial
3: Option Board (CN5)
Z1-09
10.0 Hz
HAND Mode Frequency Reference
Hand Fref
This is the frequency reference used when the
Drive is running in HAND mode.
Z1-37
0
Set Time
Set Time
Changes the LCD display to time setting to set
the Real Time Clock.
0: Normal display
1: Set date and time
2: Reset time
Motor
E1-03
F
V/f Pattern Selection
V/F Selection
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 50 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f
Note: E1-05 Max Voltage setting defi nes the V/f
pattern for settings 0 thru E..
E2-01
Model
Dep.
Amps
Motor Rated Current
Motor Rated FLA
Sets the motor nameplate full load current in
amps. Automatically set during Auto-Tuning.
E2-03
Model
Dep.
Amps
Motor No-Load Current
No-Load Current
Sets the no-load current for the motor.
Automatically set during Auto-Tuning.
Network Communication
Note: Cycle power after changing network communication parameters (Z3-XX).
Z3-01
3
Serial Communications Protocol Select
Serial Protocol
Selects the bypass serial communications
protocol.
0: Modbus
1: N2
2: P1
3: BACnet
Verify Common Parameters (continued)
8
STEP