Devicenet status leds, Setup requirements on the network master – Yaskawa MP940 Hardware Manual User Manual
Page 34

MotionSuite™ MP940 Machine Controller Hardware Manual
Section 5: Communications
31
DeviceNet Status LEDs
There are two status LEDs above the network connector. Their display is either green or
red, depending on the current status. The left LED is MS (Module Status), and the right
LED is NS (Network Status).
Setup Requirements on the Network Master
Input/output size can be less, but the settings must agree on both master and slave
setup configuration.
Module Status
Network Status
Explanation
Troubleshooting
solid green
solid green
Normal running condition
No action required.
flashing green
flashing green
No network power (24V)
Check the connection state of
the rack and system bus cable
connectors.
solid green
flashing red
No response received from
DeviceNet master
Check the connection state of
the rack and system bus cable
connectors.
Check the baud rate setting of
each device.
Check the resistance and
mounting of the termination
resistor (121 ohms).
Check the operation of the
DeviceNet master.
solid red
OFF
Hardware defect
Replace module.
solid red
solid red
Hardware defect
Replace module.
Strobed
No
Polled I/O
Yes
Explicit
No
Input Size
256 bytes (maximum)
Output Size
256 bytes (maximum)