beautypg.com

Devicenet status leds, Setup requirements on the network master – Yaskawa MP940 Hardware Manual User Manual

Page 34

background image

MotionSuite™ MP940 Machine Controller Hardware Manual

Section 5: Communications

31

DeviceNet Status LEDs

There are two status LEDs above the network connector. Their display is either green or
red, depending on the current status. The left LED is MS (Module Status), and the right
LED is NS (Network Status).

Setup Requirements on the Network Master

Input/output size can be less, but the settings must agree on both master and slave
setup configuration.

Module Status

Network Status

Explanation

Troubleshooting

solid green

solid green

Normal running condition

No action required.

flashing green

flashing green

No network power (24V)

Check the connection state of
the rack and system bus cable
connectors.

solid green

flashing red

No response received from
DeviceNet master

Check the connection state of
the rack and system bus cable
connectors.
Check the baud rate setting of
each device.
Check the resistance and
mounting of the termination
resistor (121 ohms).
Check the operation of the
DeviceNet master.

solid red

OFF

Hardware defect

Replace module.

solid red

solid red

Hardware defect

Replace module.

Strobed

No

Polled I/O

Yes

Explicit

No

Input Size

256 bytes (maximum)

Output Size

256 bytes (maximum)