Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD 506/P5 to F7 User Manual
Page 46

Appendix 3- Parameter Cross Reference
PL.F7.05 Page
46
of 54
GPD506/P5 Parameter
F7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
048
Terminal FV gain
Set unit: 1% and set range: 0 to 200%
0.0 to1000.0
Sets the output level when 10V is input, as
a percentage of the maximum output
frequency (E1-04).
Terminal A1 Gain Setting
H3-02
049
Terminal FV bias
Set unit: 1% and set range = -100 to +100%
–100.0 to +100.0
Sets the output level when 0V is input, as a
percentage of the maximum output
frequency (E1-04).
Terminal A1 Bias Setting
H3-03
050
Terminal FI gain
Set unit: 1% and set range: 0 to 200%
0.0 to 1000.0
Sets the output level when 10V is input.
Terminal A2 Gain Setting
H3-10
051
Terminal FI bias
Set unit: 1% and set range -100 to +100%
–100.0 to+100.0
Sets the output level when 0V is input.
Terminal A2 Bias Setting
H3-11
052
Analog output
Select
(terminal AM-AC)
0: Output frequency
(10V = Max frequency n011)
1: Output current
(10V = rated current of inverter)
2: Output power (10V = inverter rated power)
3: DC bus voltage (10V = 1150VDC)
Selects which monitor will be output on
terminals FM and FC.
1: Frequency Reference
100% = Maximum output frequency
2: Output Frequency
100% = Maximum output frequency
3: Output Current
100% = Drive rated current.
5: Motor Speed
100% = Maximum output frequency
6: Output Voltage
100% = 200/400Vac depending on Drive
voltage rating.
7: DC Bus Voltage
100% = 400/800Vdc depending on Drive
voltage rating.
8: Output kWatts
100% = Drive rated power.
9: Torque Reference
100% = Motor rated torque.
15: Terminal A1 Input Level
100% = 10Vdc
16: Terminal A2 Input Level
100% = 10Vdc or 20mA
17: Terminal A3 Input Level
100% = 10Vdc
18: Motor Secondary Current
100% = Motor rated secondary current.
19: Motor Excitation Current
100% = Motor rated secondary current.
20: SFS Output
100% = Maximum output frequency
21: ASR Input
100% = Maximum output frequency
22: ASR Output
100% = Maximum output frequency
24: PID Feedback
100% = Maximum output frequency.
26:Output Voltage Reference Vq
100% = E1-05, default 240V or 480V.
27: Output Voltage Reference Vd
100% = E1-05, default 240V or 480V.
31: Not Used
36: PID Input
100% = Maximum output frequency
37: PID Output
100% = Maximum output frequency
38: PID Setpoint
100% = Maximum output frequency
45: Feedforward Control Output
100% = Motor rated secondary current.
Terminal FM Monitor
Selection
H4-01
053
Analog output gain
Set unit: 0.01 and set range: 0.01-2.00
0.0 to 1000.0
Sets terminal FM output level when
selected monitor is at 100%.
Terminal FM Gain Setting
H4-02