Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD 506/P5 to F7 User Manual
Page 39

Appendix 3- Parameter Cross Reference
PL.F7.05 Page
39
of 54
GPD506/P5 Parameter
F7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
to all frequency reference sources.
033
Rated motor current
Set unit: 0.1A (In 1000A or more, every 1A)
Set range:10-200% of drive rated current
Set to the motor nameplate full load current
in amperes (A). This value is automatically
set during Auto-Tuning.
Motor Rated Current
E2-01
034
Motor protection selection
(OL1)
0: Disabled.
1: Standard motor (eight minutes)
2: Standard motor (five minutes)
3: Inverter rated motor (eight minutes)
4: Inverter rated motor (five minutes)
Sets the motor thermal overload protection
(OL1) based on the cooling capacity of the
motor.
0: Disabled
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (
≥10:1 motor)
3: Vector Motor (
≤1000:1 motor)
Motor Overload Protection
Selection
L1-01
035
Cooling fin overheat
Stop method
selection
0: Deceleration stop
(Decelerate by deceleration time 1)
1: Coast to stop
2: Deceleration stop
(Decelerate by deceleration time 2)
3: Operation continues
(The alarm is displayed, and drive runs at
80% of the freq ref)
Selects the Drive operation upon an OH
pre-alarm detection.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Overheat Pre-Alarm
Operation Selection
L8-03
036
Multi-function
contact input 1
(terminal S2)
0: REV command (2wire sequence selection)
1: FWD/REV Command
(3wire sequence selection)
2: External fault. (N.O contact input)
3: External fault. (N.C contact input)
4: Fault reset
5: LOCAL/REMOTE switch
(run and freq ref)
6: Communication/Control circuit terminal
switch (run and freq ref)
7: Emergency stop (N.O. contact input)
8: Emergency stop (N.C contact input)
9: FV/FI terminal switch
10: Multistep speed set 1
11: Multistep speed set 2
12: Multistep speed set 3
13: Jog frequency select
14: Accel/decel time switch
15: External base block instruction
(N.O.contact input)
16: External base block instruction
(N.C contact input)
17: Speed search command from Max
frequency
18: Speed search command from set
frequency
19: Parameter set enable/disable
20: PID integral value reset
21: PID control disable
22: Timer start command
23: Inverter overheat
(blinking display of OH3)
24: Sample/holding of analog reference
25: KEB instruction (N.O. contact)
26: KEB instruction (N.C. contact)
27: Decel/accel prohibit
28: PID input characteristic switchover
Terminal S2 is not
programmable in F7 :
F7 default setting for terminal
S2:
Reverse run when closed,
stopped when open.
Initialization parameter
A1-03 programs terminals
S1 and S2 for 2-Wire or
3-Wire run control.
-
037
Multi-function
contact input 2
(terminal S3)
Set range: 2-28
(It is the same as constant n036)
0 to 78
Selects the function of terminal S3.
0: 3-wire control
FWD/REV selection for 3-wire
sequence.
1: Local/Remote Selection
2: Option/Inv Selection
Selects source of frequency reference and
sequence. Closed = Option Card,
Open = b1-01 & b1-02.
3: Multi-Step Frequency Reference 1
4: Multi-Step Frequency Reference 2
Multi-Function Digital Input
Terminal S3 Function
Selection
H1-01