Product transition guide terminal comparison – Yaskawa GPD 506/P5 to F7 User Manual
Page 17

Product Transition Guide
Terminal Comparison
PL.F7.05 Page
17
of 54
GPD506/P5 Terminal
F7 Terminal
(Designations similar to GPD506/P5)
Type
GPD506/P5
Terminal
Default Function & Description
F7
Terminal
Default Function
F7 Description
MC
Fault when closed between
terminals MA and MC
Fault when open between
terminals MB and MC
Multi-function contact output
(n041)
Dry contact capacity:
250VAC 1A or less
30VDC 1A or less
MC
1 A max. at 250Vac
1 A max. at 30Vdc
AM
Frequency meter output
0 to +10V/100% frequency
Multi-function analog monitor 1
(n052)
0 to +10V
2mA or less
FM
Output frequency
0 to +10Vdc or
+/-10Vdc 500 ohm input
10V=100% Output frequency
(Max current 2mA).
4 to 20mA
20mA=100% Output
frequency
Function set by H4-01.
–
–
AM
Output current
0 to +10Vdc or
-10 to +10Vdc 500 ohm input
10V=100% Drive output
current (Max current 2mA)
4 to 20mA / 100%
Drive's rated output current /
Function set by H4-04.
Anal
og Out
put
Si
gnal
s
AC
Frequency meter output “AM”
Common
AC
Analog common
–
–
–
RP
Pulse input
1 to 32kHz (3k ohms) ±5%
High level voltages 3.5 to 13.2
Low level voltages 0.0 to 0.8
Duty Cycle (on/off) 30% to
70% Function set by H6-01.
Pulse I/O
–
–
MP
Pulse monitor
0 to 32kHz
+5V output
(Load: 1.5k ohms)
Function set by H6-06.
–
–
R+
–
–
R-
Modbus communication
Differential input,
PHC isolation
–
–
S+
–
–
S-
Modbus communication
Differential output,
PHC isolation
–
R
S
-485/
422
–
–
IG
Signal common
–